Vector SIMOVERT MASTERDRIVES 6SE70 VC Manuale Utente Pagina 46

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 57
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 45
Page 46 Version 1.0 March 1, 2000
P571 = 0
P318 = 95
P052 = 21
P052 = 0
P571=0 Selects Autotransformer
P318 = 95%
Selects percentage of nominal
DC BUS voltage. In cases where
the input line voltage is
dependable a setting of 100% is
permissible.
With DC BUS connected to the
COMMON DC BUS of the system, set
P52=21 and provide a start command
at terminal X101, pin #9
The circuit identification test will take
about 10 seconds.
P052=0 Drive back to ready mode.
Standard Commissioning for a
Regenerative Rectifier with
Autotransformer is complete, after
adjusting only 10 parameters.
Vedere la pagina 45
1 2 ... 41 42 43 44 45 46 47 48 49 50 51 ... 56 57

Commenti su questo manuale

Nessun commento